Permit Number: T05CM04018
Parcel: 117066690

Address:
477 E LAOS ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T05CM04018
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2005 GERRY KOZIOL WWM REVIEW Approved
08/18/2005 NEAL SAUNDERS BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project T05CM04018

Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pen or pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes.

Floor Plan

1. Provide tempered glass at window at master bathtub.
2. Winders stair depth minimum per R311.5.3.2. Also, B/4 - 10" stair depth @ 12", show dimension in this detail.
3. Show that each water closet is located in a clear space not less than 30" wide and has a clear space in front not less than 21" per figure R307.2.

Structural Plan

1. Locate bearing points for stairs on foundation and second story - note connections at each location. Are stairs pre-manufactured? If not provide construction details.
2. 13/10 at back porch beam should be 15/10.
3. Specify roof connection to 2nd story balcony roof beam or callout 6/10 (sim).
4. Floor framing plan suggests a bearing point at both of the middle posts on the front porch/balcony assembly. The elevations show only one of these middle posts as bearing (half post). As a corollary, the 6x8 beam at the front porch is inadequate for 15.5' span and 4' of floor tributary width.
5. Callout lintel over master bedroom door.

Plumbing and Electrical Plan

1. Isometric is lacking both upstairs tubs and one lavatory in hall bath.
2. Circuit 21 in downstairs half bath must be 20amp.
3. Outdoor lighting code specifies 4 'A' fixtures. Locate 'A' fixtures. My count is 6 outdoor lights. Clarify. Note if lights are unshielded or FCO. Also, reference 5.1.2 of the code for FCO lights under porch exclusion.

If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/22/2005 KMEDINA1 OUT TO CUSTOMER Completed