Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM03995
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/05/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/05/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the building pressurization is to be accommodated (250 CFM of net exhaust from the building). Reference Sections 403.1 and 508.1, IMC 2000. 2. Show that the equipment is being installed in accordance with the conditions of its listing and the manufacturer's installation requirements with regard to the mixed air temperature at the evaporator coil. Reference Section 304.1, IMC 2000. 3. Provide structural calculations and the weight of the hood to show that the Type I hood is supported in accordance with Section 507.6, IMC 2000. |
08/05/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the new water piping relates to the existing water supply system and show that the additional connections do not cause the existing piping to be overloaded. Reference Section 101.5.1, UPC 1994. 2. Coordinate the water connections shown on the plumbing plan with the equipment schedule shown on sheet A2.2. |
08/10/2005 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
08/10/2005 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
08/10/2005 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
08/10/2005 | CAGUILA1 | WWM | REVIEW | Needs Review |