Permit Number: T05CM03995
Parcel: 12406151B

Address:
187 N PARK AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03995
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2005 ROBERT SHERRY WATER REVIEW Approved
08/05/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the building pressurization is to be accommodated (250 CFM of net exhaust from the building). Reference Sections 403.1 and 508.1, IMC 2000.
2. Show that the equipment is being installed in accordance with the conditions of its listing and the manufacturer's installation requirements with regard to the mixed air temperature at the evaporator coil. Reference Section 304.1, IMC 2000.
3. Provide structural calculations and the weight of the hood to show that the Type I hood is supported in accordance with Section 507.6, IMC 2000.
08/05/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the new water piping relates to the existing water supply system and show that the additional connections do not cause the existing piping to be overloaded. Reference Section 101.5.1, UPC 1994.
2. Coordinate the water connections shown on the plumbing plan with the equipment schedule shown on sheet A2.2.
08/10/2005 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review
08/10/2005 CAGUILA1 ZONING REVIEW Needs Review
08/10/2005 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/10/2005 CAGUILA1 WWM REVIEW Needs Review