Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM03993 8/2/05

1. Adjusted Load Calculations on Sheet E1.1 document a total of 19,695 VA. This is not possible, because new load, according to the Panel Schedule, is 22,175, before taking into account existing loads as documented on this panel. Provide Panel A total load calculation, including new and existing.
2. Provide information sufficient to document that Vacuum System is cord-connected, and specify its power requirements.
3. Provide information sufficient to document that the X-Ray is cord-connected. We have not seen such an item as yet, and can not visualize how the requirements of NEC 517 Part V would be met for X-Ray Installations.
08/02/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the outside air calculation to comply with
the requirements of Section 403.3, IMC 2000.
Justify the classifications of the individual
rooms per Table 403.3, IMC 2000.
2. Revise the duct insulation to comply with Chapter
8, IECC 2000.
08/02/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Complete the plumbing plans and schedules.
2. Provide information regarding the vacuum system.
3. Clarify the basis of the water pressure calculations.
Reference Section 610.4, UPC 1994.
08/04/2005 JMORALE1 WWM REVIEW Needs Review