Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM03993
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/29/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Complete the plumbing plans and schedules. 2. Provide information regarding the vacuum system. 3. Clarify the basis of the water pressure calculations. Reference Section 610.4, UPC 1994. |
| 07/29/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/29/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/29/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 07/29/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the outside air calculation to comply with the requirements of Section 403.3, IMC 2000. Justify the classifications of the individual rooms per Table 403.3, IMC 2000. 2. Revise the duct insulation to comply with Chapter 8, IECC 2000. |
| 07/29/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM03993 7/29/05 1. Clarify power requirements of New Lighting Fixture 1. 2. On the Electrical Lighting Plan, clarify which lighting fixture is represented by the small circular symbol. 3. Provide total load on Panel A, not just new load. 4. Note that the divisor for a 120V circuit is 120, not 180. 5. Add the following note in a prominent place on the plans: "All wiring in patient care areas shall be installed in accordance with the requirements of NEC 517.13." 6. Plumbing plans Sheet P1.1 shows a Water Heater Schedule which is not filled. Clarify intent on P1.1 and electrical plans. 7. Plumbing Comment #2 addresses a vacuum system. If such system needs electrical power, provide for such on electrical plans. 8. Panel A has an X-Ray on Ckt 37/39. Show such equipment on the plans. |
| 07/29/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/02/2005 | JMORALE1 | WWM | REVIEW | Needs Review |