Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/29/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
07/29/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
07/29/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/29/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/29/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
07/29/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information to show that the ventilation for the space complies with Section 403, IMC 2000. |
07/29/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM03992 7/29/05 1. Add continuous loads to panel schedule calculations. 2. Add largest motor to feeder (panel schedule) calculations. |
07/29/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
08/01/2005 | GERRY KOZIOL | WWM | REVIEW | Approved |