Permit Number: T05CM03968
Parcel: 11305066D

Address:
1802 E PRINCE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03968
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the water pressure calculations per Appendix A. Based on the information shown some of the pipe sizes are not adequate for the demand. Reference Section 610.5, UPC 1994.
09/30/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Coordinate the locations of the rooftop units shown on the structural drawing (S-3) with the mechanical drawing (M-1). Reference Section 302.1, IMC 2000.
2. The provided ventilation calculation assumes that all of the additional floor area is composed of patient exam rooms, neglecting the reception room. Provide calculations demonstrating adequate ventilation based on the various room types shown in Table 403.3. Reference Sections 403.3 and 403.3.2, IMC 2000.
10/07/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 10/10/05
ACTIVITY NUMBER: T05CM03968
PROJECT NAME: Addition Carol McGonigle, D.D.S.
PROJECT ADDRESS: 1802 E. Prince Rd.
ARCHITECT / ENGINEER: Thomas Panno
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) It appears actual sq. footage of building equals 4000-sq. ft. Please clarify and adjust occupant load accordingly.
2) Please show circular clear floor space in each handicap restroom see ANSI A117.1 2003 section 304.3.1. Door swing in clear floor space, see section 603.2.3 exception 2. Provide one accessible restroom per sex minimum.
3) Clarify accessibility from parking into building. Show striped path from parking to sidewalk. Provide ramp at grade change and aceesible route to entry and then to restroom facilities. It appears it would be better to have handicap parking located near the new entry to help eliminate the danger of being hit by vehicles just entering the site.
4) Entry joists need to be specified on sht. S-3 Roof Framing Plan.
5) Clarify justification for footings specified on drawings S-2.
6) Specify footing sht. S-2 at entry pier per structural calculations page 15.
7) Justify column members at entry with structural calculations.
8) Clarify roof framing can carry additional load of mechanical equipment.
10/10/2005 JOSE ORTIZ ENGINEERING REVIEW Denied Will be approved upon final approval of the site plan.

If you have any questions, I can be reached at 791-5550 x1191 Jose.Ortiz@tucsonaz.gov
10/25/2005 MICHAEL ST. PAUL ZONING REVIEW Denied Site plan approval required.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/09/2005 GBONILL1 OUT TO CUSTOMER Completed
11/09/2005 SUE REEVES REJECT SHELF Completed