Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM03968
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/02/2005 | ASHOFFS1 | FIRE | REVIEW | Approved | |
| 08/02/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Include all fixtures (e.g. the new exam sinks, existing hoe bibbs) when calculating the total demand and determining pipe sizes. Reference Section 610.1, UPC 1994. 2. Include the total developed pipe length (from the water meter to the furthest water outlet) when performing the water pressure calculations. Reference Appendix A, UPC 1994. 3. Revise the route of the T&P relief pipe from the water heater to avoid creating a trap. Reference Section 608.5, UPC 1994. 4. Show how the new water piping relates to the existing water supply system and show that the additional connections do not cause the existing piping to be overloaded. Reference Section 101.5.1, UPC 1994. 5. Show how the requirement for a drinking fountain has been addressed. Reference Section 2902.1, IBC 2003. |
| 08/02/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/02/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Demonstrate energy code compliance using calculations based on the current code. Reference Section 101.3, International Energy Conservation Code 2000. 2. Coordinate the locations of the rooftop units shown on the structural drawing (S-1) with the mechanical drawing (M-1). Reference Section 302.1, IMC 2000. 3. Provide calculations demonstrating adequate ventilation based on the various room types shown in Table 403.3. Reference Sections 403.3 and 403.3.2, IMC 2000. |
| 08/16/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 08/23/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/24/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | Site approval required. |
| 08/25/2005 | JOSE ORTIZ | ENGINEERING | REVIEW | Denied | Final approval pending the approval of the site plan. If you have any questions, I can be reached at 791-5550 x1191 Jose.Ortiz@tucsonaz.gov |
| 09/06/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 9/2/05 ACTIVITY NUMBER: T05CM03968 PROJECT NAME: Addition Carol McGonigle, D.D.S. PROJECT ADDRESS: 1802 E. Prince Rd. ARCHITECT / ENGINEER: Thomas Panno PROJECT REVIEWER: Christy Foreman TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1) It appears actual sq. footage of building equals 4000-sq. ft. Please clarify and adjust occupant load accordingly. 2) Please show circular clear floor space in each handicap restroom see ANSI A117.1 2003 section 304.3.1. Door swing in clear floor space, see section 603.2.3 exception 2. Provide one accessible restroom per sex minimum. 3) Clarify accessibility from parking into building. 4) Entry joists need to be specified on sht. S-3 Roof Framing Plan. 5) Clarify justification for footings specified on drawings S-2. 6) Specify footing sht. S-2 at entry pier per structural calculations page 15. 7) Justify column members at entry with structural calculations. 8) Clarify roof framing can carry additional load of mechanical equipment. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/07/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 09/07/2005 | SUE REEVES | REJECT SHELF | Completed |