Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Address on the plans is 3626 N Oracle. Does not conform to address on Permit Application, that being 3623 N Oracle. Please clarify.
2. Incorporate Site Plan and Load calculations on engineered plans, not as a half-sized, separate document.
3. Holophane cut sheets do not demonstrate full-cutoff lighting distribution of the intended fixture. Reference Tucson Lighting Code 6.1 and 4.7.
4. Put Lighting Schedule on engineered plans, not as a letter-sized, separate document. Document submitted has no reference to this project, not an address, not dated, responsible party not identified.
5. Specify controller to be installed in compliance with Tucson Lighting Code 6.2, and Table 6.4 Note 2. If such controller is existing, state so on the plans.
6. Provide a Lighting Fixture schedule on the plans, including but not limited to such information as lighting source type, voltage, wattage, mounting, lighting distribution characteristics, catalogue cut number.
7. Provide photometric data from the manufacturer, showing angle of cutoff. Reference Tucson Lighting Code 8.1.3.
02/16/2006 JRUBALC1 ZONING REVIEW Stop
07/27/2005 CHUCK STEPHENSON SIGNS SIGN CODE REVIEW Stopped
07/27/2005 ANY BUILDING-COMMERCIAL REVIEW Stopped