Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T05CM03937
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/23/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/25/2005 | JIM EGAN | FIRE | REVIEW | Denied | 1. Fire sprinkler riser detail Sheet FP 2.1 is incorrect. Correct riser detail or remove Sheets FP1.0, FP2.0 and FP2.1 from plans. 2. Separate plan submittals and permits are required for installation of Fire Sprinklers, Fire Sprinkler Underground Piping and Kitchen Exhaust Hood Fire Suppression Systems. Remove items 2 and 3 from "Fire Alarm System General Notes" Sheet T0.1. |
11/28/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | needs to show method/location of connection to public sewer. needs manhole tap permit. needs to abandon 8" public sewer. needs 8th floor credit evaluation. |
12/05/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
12/06/2005 | DAN CASTRO | ZONING | REVIEW | Denied | A copy of the stamped approved site plan must be inserted into each building plan set to obtain zoning review approval. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/14/2005 | GBONILL1 | OUT TO CUSTOMER | Completed |
12/14/2005 | SUE REEVES | REJECT SHELF | Completed |