Permit Number: T05CM03933
Parcel: 12504083C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03933
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2005 JIM EGAN FIRE REVIEW Approved
07/27/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/27/2005 ANY BUILDING-COMMERCIAL REVIEW Denied S1. ADDRESS ACCESSIBILITY.
07/27/2005 ROBERT SHERRY WATER REVIEW Approved
07/27/2005 JOSE ORTIZ ENGINEERING REVIEW Approved
07/27/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide mechanical exhaust for the restroom. Reference footnote B, Table 403.3, IMC 2000.
08/08/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM03933 7/27/05

1. There is no Insta-Hot as required by Plumbing plans. Coordinate with Plumbing and clarify.
2. Please note that the Mechanical Plans examiner has required the addition of an EF.
3. Please count 200 VA/LF for show window receptacles. Reference NEC 220.3 (B) (7).
4. Minimum font size is 1/8". Please enlarge as necessary.
5. Provide location of existing service on a scaled drawing, such that the distance to the new panel may be verified.
6. F1 would be right at the point of delivery per SR-510, not 120 feet away.
08/08/2005 CAGUILA1 WWM REVIEW Passed
08/08/2005 CAGUILA1 ZONING REVIEW Needs Review