Review Details: COMMERCIAL TI
Permit Number - T05CM03933
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/27/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/27/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/27/2005 | ANY | BUILDING-COMMERCIAL | REVIEW | Denied | S1. ADDRESS ACCESSIBILITY. |
| 07/27/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/27/2005 | JOSE ORTIZ | ENGINEERING | REVIEW | Approved | |
| 07/27/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide mechanical exhaust for the restroom. Reference footnote B, Table 403.3, IMC 2000. |
| 08/08/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM03933 7/27/05 1. There is no Insta-Hot as required by Plumbing plans. Coordinate with Plumbing and clarify. 2. Please note that the Mechanical Plans examiner has required the addition of an EF. 3. Please count 200 VA/LF for show window receptacles. Reference NEC 220.3 (B) (7). 4. Minimum font size is 1/8". Please enlarge as necessary. 5. Provide location of existing service on a scaled drawing, such that the distance to the new panel may be verified. 6. F1 would be right at the point of delivery per SR-510, not 120 feet away. |
| 08/08/2005 | CAGUILA1 | WWM | REVIEW | Passed | |
| 08/08/2005 | CAGUILA1 | ZONING | REVIEW | Needs Review |