Permit Number: T05CM03930
Parcel: 129010360

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03930
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2005 ANY ENGINEERING REVIEW Approved
07/27/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
07/28/2005 GERRY KOZIOL WWM REVIEW Passed
07/29/2005 JIM EGAN FIRE REVIEW Approved
07/29/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show that the revision to the gas piping in room 127 will not adversly affect ther existing gas piping.
07/29/2005 ROBERT SHERRY WATER REVIEW Approved
07/29/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1.Show that adequate ventilation is being provided to the classrooms per Section 403.3, IMC 2000. Justify the "maximum" population of 20 per classroom.
2. Show the termination of the condensate piping.
3. Clarify the reason for the different flue sizes.
08/11/2005 EGRANT1 BUILDING-COMMERCIAL REVIEW Needs Review
08/11/2005 EGRANT1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2005 BETH GRANT OUT TO CUSTOMER Completed