Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM03930
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/27/2005 | ANY | ENGINEERING | REVIEW | Approved | |
07/27/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
07/28/2005 | GERRY KOZIOL | WWM | REVIEW | Passed | |
07/29/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
07/29/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show that the revision to the gas piping in room 127 will not adversly affect ther existing gas piping. |
07/29/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/29/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1.Show that adequate ventilation is being provided to the classrooms per Section 403.3, IMC 2000. Justify the "maximum" population of 20 per classroom. 2. Show the termination of the condensate piping. 3. Clarify the reason for the different flue sizes. |
08/11/2005 | EGRANT1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
08/11/2005 | EGRANT1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/11/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |