Permit Number: T05CM03910
Parcel: 133231420

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03910
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2005 JIM EGAN FIRE REVIEW Approved
07/26/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/26/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
07/26/2005 ROBERT SHERRY WATER REVIEW Approved
07/26/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
07/26/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show the extent of the mechanical demolition
07/26/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM03910 7/26/05

1. Provide power requirements for Fixture 1.

2. Provide power requirements for Fixture 2.

3. Track lighting feeders shall be counted at 75 VA/LF per NEC 220.12 (B). However, you might use the maximum VA of the transformer if this is for low voltage. In that case, make it clear on the plans how many transformers shall be on each circuit.

7/28/05
Comment #3 above not satisfied with respect to continuous load. Mis-calculation on Ckt 21.
07/26/2005 DOUG WILLIAMS ENGINEERING REVIEW Approved
07/28/2005 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2005 KMEDINA1 OUT TO CUSTOMER Completed