Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM03910
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/26/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/26/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/26/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/26/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/26/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/26/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show the extent of the mechanical demolition |
| 07/26/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM03910 7/26/05 1. Provide power requirements for Fixture 1. 2. Provide power requirements for Fixture 2. 3. Track lighting feeders shall be counted at 75 VA/LF per NEC 220.12 (B). However, you might use the maximum VA of the transformer if this is for low voltage. In that case, make it clear on the plans how many transformers shall be on each circuit. 7/28/05 Comment #3 above not satisfied with respect to continuous load. Mis-calculation on Ckt 21. |
| 07/26/2005 | DOUG WILLIAMS | ENGINEERING | REVIEW | Approved | |
| 07/28/2005 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/28/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |