Permit Number: T05CM03908
Parcel: 13219015B

Address:
2200 E BENSON HY

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T05CM03908
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2005 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Landscaping is required along retention basin side slopes, bottom and periphery. Plant materials used in basins shall withstand periodic inundation. A minimum of 20 trees per acre must be provided, 33% of tress shall be 24" box or larger. A minimum of 2 shrubs for each tree is required per DS 10.01. Revise landscape plan to include the entire basin treatment.

2. Note: Multi-use basins shall be required to conform to the following slope to depth ratios: Less than 3' Maximum 2:1 for protected side slopes and 3:1 for unprotected side slopes. Include basin detail on landscape plan indicating side slope protection and demonstrate landscape installation within basin.
09/16/2005 ANDREW CONNOR NPPO REVIEW Approved
09/28/2005 DAN CASTRO ZONING REVIEW Denied COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The legal description listed on the plan appears to describe the adjacent property. Note the legal description of the subject property. (D.S. 2-02.2.1.A.2)

2. Provide a copy of the cross access agreement for zoning review. The cross access agreement/easement shall be recorded prior to site plan approval. The recordation information (docket and page) shall be noted on the site plan. (D.S. 2-02.2.1.A.12)

3. Label zoning classification (C-2) of adjacent properties on the plan. (D.S. 2-02.2.1.A.28)

4. Provide the proposed F.A.R.

5. Access across the adjacent property will require that the PAAL on the adjacent property be paved where providing access to the subject property. Add a note to this effect. If the adjacent property is being developed concurrently with the subject property, add a note, which explains this and list the permit activity number for the adjacent property within its lot boundaries. If the adjacent property is not being developed at this time, a barrier will be required to prevent vehicles entering the subject property from encroaching onto unimproved portions of the adjacent property.

6. Under general note six (6), correct the zoning from I-1 to C-2.

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608 ext. 1180. An appointment is required to discuss these comments in person.
09/29/2005 DAN CASTRO ZONING HC SITE REVIEW Approved
09/29/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Thomas Panno DATE: September 30, 2005
Architects
8042 E. Hayden Place
Tucson, Arizona 85715

SUBJECT: 2200 E. Benson Hwy., Caylor Industrial
Site plan T05CM03908 (First Review)
T14S, R14E, Section 32

RESUBMITTAL REQUIRED: Site Plan.

The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. The inside dimensions of the refuse enclosure shall be 10'x10' clear area for the dumpster. The min. turning radii is 34' and 50' respectively. Contact Environmental Services @ 791-5543 x1136, John Clark, for approval of refuse enclosure.

Drainage Report:
1. The DR has been accepted for site plan purposes only.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/2200 E Benson Hwy Site 2

Final Status

Task End Date Reviewer's Name Type of Review Description
10/03/2005 JMORALE1 OUT TO CUSTOMER Completed
10/03/2005 JMORALE1 REJECT SHELF Completed