Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM03908
Parcel: 13219015B

Address:
2200 E BENSON HY

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM03908
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2005 JIM EGAN FIRE REVIEW Approved
08/02/2005 DAN CASTRO ZONING REVIEW Denied Zoning Review Section may not approve the building plans prior to site plan approval. Site plan is currently under review. Please assure that all structures shown on the building plans match the location, size, and height on the site plan.
08/25/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Thomas Panno DATE: August 29, 2005
Architects 8042 E. Hayden Place
Tucson, Arizona 85715

SUBJECT: 2200 E. Benson Hwy., Caylor Industrial
Site plan T05CM03908 (First Review)
T14S, R14E, Section 32

RESUBMITTAL REQUIRED: Site Plan and Drainage Report.

The Site Plan (SP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. An appointment with the reviewer may be necessary to discuss the excessive omissions to the submittal prior to the next review. Contact Elizabeth Eberbach or Paul Machado at 791-5550.
3. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207.
4. Please provide North arrow and scale per D.S. 2-02.2.1.
5. Complete the location plan with the pertinent information.
6. Please provide property description per D.S. 2-02.2.1.3.
7. Provide all existing and proposed buildings and structures, including location, size, height, overhangs, canopies, and use per D.S. 2-02.2.1.6.
8. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
9. Show all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.
10. Please label all vehicular, bicycle, pedestrian, and handicapped circulation clearly identified per D.S. 2-02.2.1.12.
11. Fully dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14.
12. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
13. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.
14. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the SP.
15. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
16. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and a Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23. The information for the BM must be shown on the plans.
17. Show all fences, walls, or vegetation for screening and sight visibility by type, material, height, location and spacing per D.S. 2-02.2.1.27.
18. Show City of Tucson activity plan number on all sheets per D.S. 2-02.2.1.29.
19. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0.
20. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
21. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
22. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
23. List the consulting engineer and the owner/developer on the plans with the pertinent information.
24. "A grading permit and a Stormwater Pollution Prevention Plan (SWPPP) will be required for this project. Submit 3 sets of grading and SWPPP's plans with text, upon completion and submittal of a grading permit application. A grading permit may not be issued prior to site plan approval. Subsequent comments may be necessary, depending upon the nature and extent of revisions to the plans". Contact Paul P. Machado at 791-5550 x1193.
Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. A Drainage report is required for any site greater than one acre in size or for any site subject to detention requirements…..per S.M.D.D.F.M., chap. II, 2.1.2.
3. Detention as will as Retention are required for this project.
4. The content and format of the Drainage Report should follow S.M.D.D.F.M., chap. II, 2.2.
5. Show the project address or administration address on the cover sheet of the DR.
6. If applicable, add the basin(s) maintenance responsibility note and checklist per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DR.
If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax, C:/2200 E Benson Hwy Site
08/30/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) DETAIL 7/S-3 DOES NOT MATCH WITH WHAT IS SPECIFIED ON SHT. 3 OF THE STRUCTURAL CALCULATIONS. 12" HOOK AROUND BOLTS IS NOT CONSIDERED.