Permit Number: T05CM03858
Parcel: 140420280

Address:
7051 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03858
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2005 JIM EGAN FIRE REVIEW Approved
07/22/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/22/2005 TERRY STEVENS ZONING REVIEW Approved
07/22/2005 GERRY KOZIOL WWM REVIEW Passed
07/22/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
07/22/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/22/2005 ROBERT SHERRY WATER REVIEW Approved
07/29/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t05cm03858 7/29/05

1. Minimum font size 10 point, which is a little over 1/8".
2. Sheet ID-101, clarify the modifications refered to in Demolition Note 15.
3. Provide the Electrical and Mechanical drawings referenced on Sheets ID-102 and ID-104 NOTE.
4. Furnature Plan Note 8 Sheet ID-103 refers the Lighting Specifications for further instructions regarding the new duplex receptacle outlets. It is unclear how lighting specifications would pertain to such receptacles.
5. Provide a lighting fixture schedule, or specify a maximum wattage for each fixture type.
6. Demonstrate that no branch circuits, feeders, or services are being overloaded.
7. Lighting fixture specified on Keynote 7 Sheet ID-104 shall be listed for wet location.
09/01/2005 JMORALE1 BUILDING-COMMERCIAL REVIEW Needs Review