| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/22/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/22/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/22/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 07/22/2005 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 07/22/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 07/22/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 07/22/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/29/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t05cm03858 7/29/05 1. Minimum font size 10 point, which is a little over 1/8". 2. Sheet ID-101, clarify the modifications refered to in Demolition Note 15. 3. Provide the Electrical and Mechanical drawings referenced on Sheets ID-102 and ID-104 NOTE. 4. Furnature Plan Note 8 Sheet ID-103 refers the Lighting Specifications for further instructions regarding the new duplex receptacle outlets. It is unclear how lighting specifications would pertain to such receptacles. 5. Provide a lighting fixture schedule, or specify a maximum wattage for each fixture type. 6. Demonstrate that no branch circuits, feeders, or services are being overloaded. 7. Lighting fixture specified on Keynote 7 Sheet ID-104 shall be listed for wet location. |