Permit Number: T05CM03841
Parcel: 13409018B

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM03841
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2005 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review
07/21/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM03841 7/21/05

1. Indicate total lighting fixtures on plans.
2. Put lighting schedule on plans.
3. Specify voltage at which these fixtures are to operate.
4. Specify conduit and conductor size and type.
5. Provide reference for photometric data.
6. Provide a schedule on the plans demonstrating compliance with the Tucson Lighting Code.