| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2005 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 07/21/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM03841 7/21/05 1. Indicate total lighting fixtures on plans. 2. Put lighting schedule on plans. 3. Specify voltage at which these fixtures are to operate. 4. Specify conduit and conductor size and type. 5. Provide reference for photometric data. 6. Provide a schedule on the plans demonstrating compliance with the Tucson Lighting Code. |