Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM03816
Parcel: 110121020

Address:
2675 N WYATT DR

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03816
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2005 JIM EGAN FIRE REVIEW Denied 1. Provide complete fire sprinkler system design criteria on plan.
07/25/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Demonstrate energy code compliance using calculations based on the current code. Reference Section 101.3, International Energy Conservation Code 2000.
2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference Section 803.2.8, IECC 2000.
3. Show how the "non-programmable electronic thermostats" called out on sheet M-4.0 (as compared to the seven-day programmable thermostat specified on sheet M-4.1) complies with Section 803.3.3.1, IECC 2000.
4. Show that the combustion air and vent piping for the condensing furnaces has been sized in accordance with the conditions of its listing and the manufacturer's installation requirements. Reference Section 304.1, IMC 2000.
5. The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2000 or an approved engineering analysis of the specific occupancy type. Revise the outside air calculation for the multipurpose room and the offices as required. Reference Section 403.3, IMC 2000.
6. Specify the insulation for the refrigerant piping referenced on detail on sheet M-4.0. Reference Section 1107.3, IMC 2000.
07/25/2005 ROBERT SHERRY WATER REVIEW Approved
07/26/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference Section 103.2.3, UPC 1994.
2. Provide site drawing showing the size, route, and slope of the building sewer. Reference Section 103.2.3, UPC 1994.
08/12/2005 GERRY KOZIOL WWM REVIEW Passed
08/15/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T05CM03816 .. 2675 N WYATT DRIVE .. COMMONS BUILDING REMODEL AND ADDITION .. 1ST REVIEW .. DGL .. 8/26/05 ..


S1. Clarify occupancy/ies of this building, is kitchen F1?, is Multi-Purpose Room A2, A3 or other occupancy?, on drawing:
1. Explain kitchen; 1.Is the kitchen dedicated to this facility, only?, 2.Hours of operation?
2. Explain/list Multi-Purpose Room uses to determine occupancies, ie dining, community room, amusement, education, etc, and occupant load/s.
3. Is entire building I1 occupancy?
S2. Clarify longest diagonal, extend from bottom left corner of Multi-Purpose Room to top right corner of new office #121.
S3. Provide premises identification on building elevation facing the PAAL, drawing A-2.3, per IBC Section 501.2 and Pima County Addressing Ordinance requirements, also show location of site addressing at Wyatt Drive as required by Pima County Addressing Ordinance.
S4. Provide complete Allowable Area Calculation, per IBC Section 506 required on Code Review Checklist.
S5. Provide site plan dimensionally locating Commons Building from two adjacent property lines and adjacent structures.
S6. Provide drawings, details and Structural Calculations for shade structure shown on drawing A-1.2.
S7. Clarify KEY NOTES & SYMBOLS, #A8, locate 'NEW' gazebo on drawing A-1.2 and provide drawings, details and Structural Calculations for this gazebo.
S8. Provide details for fencing, including gates, swing of gates and gate hardware to show conformance with exiting requirements, explain/justify exiting control system.
S9. Provide site detail drawing A-1.4 referred to in Notes #A4 on drawing A-1.2.
S10.Clarify corridor fire-rating requirements ref IBC Section 1016 and IBC Chapter 7.
S11. Provide site plan with adequate finished grades indicated to show conformance with egress and accessibility requirements of IBC Chapter 10 and 11.
S12. Clarify by dimensioning landings to show conformance with IBC Sections 1008, 1101 and ANSI A117.1-2003ed.
S13. Provide or show exit signage in existing portion of Commons Building, per IBC Section 1011.
S14. Provide specifications for materials to be used on this project.
S15. Indicate fire classification of roof covering on drawings ref dwg A-2.2 and IBC Section 1505.
S16. Submit two sets of shop drawings and calculations, stamped and signed by an Arizona Registered engineer, shop drawings shall be reviewed by and bear the approval of the Engineer or Architect of Record prior to submission to the City of Tucson , Development Services Department for approval prior to erection for :
1. Window flashing ref Detail 1/A-5.1.
2. Prefabricated roof trusses.
S17. Provide re-evaluation of minimum plumbing fixtures on drawings to show conformance with IBC Section 29, due to increase in occupant load.
S18. Address accessibility for Commons Building per IBC Section 3409, IBC Chapter 11 and ANSI A117.1-2003ed.
S19. Provide Inspection Program as required by the 1997 Uniform Administrative Code as amended and adopted by the City of Tucson, Section 302.5.
S20. Provide Special Inspection as required by the 1997 Uniform Administrative Code as amended and adopted by the City of Tucson, Section 306 for:
1. Site preparation.
2. Foundation excavation and compaction.
3. Epoxy anchor bolts
S21. Specify on drawing S-2.2 design Equipment Loads, Dead Loads and Live Loads for the mechanical platform, provide structural calculations and details at roof and floor of platform.
S22. Provide complete Structural Design and Details for the Lateral Force-resisting system.


Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.
08/19/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. New exterior lighting shall comply with the Tucson Lighting Ordinance, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.
2. Revised load for service calculations adds 96.2A for Panel C. This figure is 181.4A according to the panel schedule.
3. Submit Lighting Power Budget for new construction per 2000 IECC.
09/02/2005 DAN CASTRO ZONING REVIEW Denied 1. The building plans may not be approved by Zoning Review until the approved development plan has a site plan approval stamp. In addition to the development plan approval stamp, sheet A-1.1 requires a site plan approval stamp. You may do an over the counter review will all applicable sections for site review compliance. A site review card may be obtained at the permit review counter to begin the process.

2. The building plans may not be approved prior to obtaining subdivision approval. Please contact Heather Thrall, Lead Planner, for information regarding the subdivision process.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/06/2005 KMEDINA1 OUT TO CUSTOMER Completed