Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM03816
Parcel: 110121020

Address:
2675 N WYATT DR

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03816
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
03/12/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/18/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.


1. Please provide a maintenance disconnecting means within sight of the whirlpool bather referenced on Keynote 3 of Sheet E-1.4. Reference NEC Article 680.12. PREVIOUS COMMENT.
2. Submit Lighting Power Budget for new construction per 2000 IECC. PREVIOUS COMMENT. PERTAINS TO THE ADDITION TO COMMONS BUILDING.