Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM03816
Parcel: 110121020

Address:
2675 N WYATT DR

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03816
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. I get a total of 240A for Panels A1, considering the load for Panel A1 as 8760 VA on Phase B, and the Air Handler at 1776 VA per phase. This corrects the final service loading to 1515.3 A, which gives the Owner more accurate information as to spare capacity on this 1600 A service.
2. Submit Lighting Power Budget for new construction per 2000 IECC.
12/14/2005 HEATHER THRALL ZONING REVIEW Approved
12/14/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T05CM03816-1 .. 2675 N WYATT DRIVE .. COMMONS BUILDING REMODEL AND ADDITION .. 2ND REVIEW .. DGL .. 12/19/05 ..


S1 See prior comment S17, see also Petition of Appeal to Building Official. (S17. Provide re-evaluation of minimum plumbing fixtures on drawings to show conformance with IBC Section 29, due to increase in occupant load.)
S2 See prior comment S18, toilet rooms in Commons Building do not appear to comply with IBC an ANSI. (S18. Address accessibility for Commons Building per IBC Section 3409, IBC Chapter 11 and ANSI A117.1-2003ed.)

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.
12/21/2005 JIM EGAN FIRE REVIEW Approved 1. Provide complete fire sprinkler system design criteria on plans.
2. Remove locking devices from gates.
12/27/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the discrepancy between the manufacturer's published data and the recommendations of the manufacturer's representative. The manufacturer's published data shows 3" vent and combustion air pipes and a 3" concentric termination required for 2001-3000 feet of elevation for the unit sizes specified (100-20). Reference Section 304.1, IMC 2000.
12/27/2005 ROBERT SHERRY WATER REVIEW Approved
12/27/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/21/2006 AOLIVO1 OUT TO CUSTOMER Completed
02/21/2006 SUE REEVES REJECT SHELF Completed