Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM03815
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/25/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/12/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Show how the Type I hood is attached to the building structure and provide structural calculations. Reference: Section 507.6, IMC 2000. (Note: include the possible weight of personnel working on or in the hood.) 2. Comment not addressed. The clearances for the Type I hood (i.e. from cabinets and other combustibles) shall conform to section 507.9, IMC 2000. Note that the wood-framed wall adjacent to the hood is not considered noncombustible by the mechanical code. |
03/12/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
03/18/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Please provide a maintenance disconnecting means within sight of the whirlpool bather referenced on Keynote 3 of Sheet E-1.4. Reference NEC Article 680.12. PREVIOUS COMMENT. 2. Submit Lighting Power Budget for new construction per 2000 IECC. PREVIOUS COMMENT. PERTAINS TO THE ADDITION TO COMMONS BUILDING. |