Permit Number: T05CM03814
Parcel: 110121020

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03814
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
03/12/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Show how the Type I hood is attached to the building structure and provide structural calculations. Reference: Section 507.6, IMC 2000. (Note: include the possible weight of personnel working on or in the hood.)
2. Comment not addressed. The clearances for the Type I hood (i.e. from cabinets and other combustibles) shall conform to section 507.9, IMC 2000. Note that the wood-framed wall adjacent to the hood is not considered noncombustible by the mechanical code.
03/12/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/18/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.


1. Please provide a maintenance disconnecting means within sight of the whirlpool bather referenced on Keynote 3 of Sheet E-1.4. Reference NEC Article 680.12. PREVIOUS COMMENT.
2. Submit Lighting Power Budget for new construction per 2000 IECC. PREVIOUS COMMENT. PERTAINS TO THE ADDITION TO COMMONS BUILDING.