Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM03812
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2005 | JOSE ORTIZ | ENGINEERING | REVIEW | Approved | |
| 10/12/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The new roof drain and overflow piping for the existing roof (Sheet A-2.0) appears to be a single pipe. Overflow drains and piping shall be independent of the primary roof drains and piping. Reference Section D 1.1 (d), UPC 1994. 2. Increase the size of the overflow in the roof drain collector boxes to equal the required size of the scupper. (The minimum opening height of a scupper is 4".) Reference Section D1.1 (d), UPC 1994. |
| 10/12/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The use of PVC pipe as a condensate drain exposed to direct sunlight is not approved. Reference Section 313.5, UPC 1994 and Section 313.3, IAPMO IS 9-92. |
| 10/27/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Minimum font size is 10 point, which is a little larger than 1/8". This effects the panel schedule most especially. 2. Please eliminate the redundant GND from the new gutter to the New 200A Meter enclosure. Reference NEC 250.24 (B). 3. Provide TEP available fault current at the terminals of the TEP Transformer. 4. Provide fault calculations for AFC at New Panel D. Plans shall stand on their own. Apply any relevant information to present plans. |
| 11/04/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Needs Review | Building approval is required before final zoning approval. |
| 11/10/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/17/2005 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 11/17/2005 | SUE REEVES | REJECT SHELF | Completed |