Permit Number: T05CM03812
Parcel: 12513020C

Review Status: Completed

Review Details: REVISION - SITE

Permit Number - T05CM03812
Review Name: REVISION - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2005 ANDREW CONNOR LANDSCAPE REVIEW Approved 1. Street landscape borders shall be located entirely on site, except that, if approved by the City Engineer or designee per LUC 3.7.2.4.3. Provide approval documentation with re-submittal.

2. Walls constructed in a single continuous line shall extend into a street landscape border no more than the actual width of the fence or wall. Where a fence or wall incorporates offsets or similar design features, a screen may extend a maximum of three 3 feet into the street landscape border per LUC 3.7.3.2.3. Move 30" wall to the back of landscape border or use offset design.

3. Within a vehicular use area, 1 canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within 40 feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.a. Provide additional trees within vehicle use area to meet requirement.
11/30/2005 ANDREW CONNOR NPPO REVIEW Approved
11/30/2005 ANDREW CONNOR LANDSCAPE REVIEW Approved comments have been addressed.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/07/2005 JMORALE1 OUT TO CUSTOMER Completed
12/07/2005 SUE REEVES REJECT SHELF Completed