Permit Number: T05CM03812
Parcel: 12513020C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03812
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/23/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/02/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please eliminate the redundant GND from the TEP transformer to the New 1200A landing can. Reference NEC 250.24 (B).
2. Fault calculations for AFC at New Panel D use a "c" value of 2430, which corresponds to that for a #6 copper conductor installed in nonmagnet conduit. The 3/0 conduit to Panel D would have a corresponding "c" value of 12844 if the conduit were metallic. This would result in a fault current which would exceed the 22K rating of the new panel. Please make the necessary corrections to both the fault calculations and panel short circuit rating.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/07/2005 JMORALE1 OUT TO CUSTOMER Completed
12/07/2005 SUE REEVES REJECT SHELF Completed