Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM03810
Parcel: 125091980

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM03810
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/03/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved