Permit Number: T05CM03810
Parcel: 125091980

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM03810
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that operating AC-17 and AC-18 at 92% outside air does not violate the manufacturer's listing for proper application due to high mixed air temperature at the evaporator coil.
2. The minimum acceptable font size is 10 points.
08/03/2005 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review