Permit Number: T05CM03807
Parcel: 13316037H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03807
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/20/2005 ROBERT SHERRY WATER REVIEW Approved
07/20/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/22/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
07/22/2005 TERRY STEVENS ZONING REVIEW Approved
07/25/2005 GERRY KOZIOL WWM REVIEW Approved
07/25/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
07/25/2005 JIM EGAN FIRE REVIEW Approved
07/25/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM03807 7/20/05

1. Provide power requirements for luminaires.
2. Demonstrate compliance with the Tucson Lighting Code. If exterior lights are replacing existing of the same lumen count, disregard.
3. New (replacement) panel does not need to be grounded if service is on the same building. If not, size the Grounding Electrode Conductor.
4. Demonstrate that the 10,000A AIC rating of the panel is adequate.

7/25/05
First Sign-In, no changes on plans.
Second sign-In, annotations on Revision to compliance.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2005 KMEDINA1 OUT TO CUSTOMER Completed