Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM03807
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/20/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/20/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/20/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/22/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 07/22/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 07/25/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 07/25/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/25/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/25/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM03807 7/20/05 1. Provide power requirements for luminaires. 2. Demonstrate compliance with the Tucson Lighting Code. If exterior lights are replacing existing of the same lumen count, disregard. 3. New (replacement) panel does not need to be grounded if service is on the same building. If not, size the Grounding Electrode Conductor. 4. Demonstrate that the 10,000A AIC rating of the panel is adequate. 7/25/05 First Sign-In, no changes on plans. Second sign-In, annotations on Revision to compliance. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/28/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |