Permit Number: T05CM03787
Parcel: Unknown

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM03787
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM03787 8/15/05

1. Provide calculations for pole and foundation. Calculations are required for any pole over 20' in height, sealed by a Registered Structural Engineer. Otherwise, plans are correct electrically. Electrical Plans Examiner will approve plans for Electrical after submittal of Structural calculations per this comment.
08/25/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE VALUATION FOR ALL SITE IMPROVEMENTS.
2) PROVIDE STRUCTURAL CALCULATIONS FOR LIGHT POLE BASES.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2005 SUE REEVES REJECT SHELF Completed