Permit Number: T05CM03778
Parcel: 133243690

Address:
100 N PANTANO RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM03778
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2005 JIM EGAN FIRE REVIEW Approved
07/21/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
07/27/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide roof drainage calculations to show that the scuppers for the existing roof provide adequate capacity. Reference Appendix D, UPC 1994.
2. Provide roof drainage calculations to show that the proposed rain gutters and downspouts provide adequate capacity to handle the drainage from both the existing roof and the new roof. Reference Appendix D, UPC 1994.
07/27/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/27/2005 ROBERT SHERRY WATER REVIEW Approved
07/28/2005 DAN CASTRO ZONING REVIEW Denied Zoning Review may not approve the building plans prior to site plan approval by all sections.
08/11/2005 GERRY KOZIOL WWM REVIEW Passed
08/17/2005 PAUL MACHADO ENGINEERING REVIEW Approved
08/19/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 8/25/05
ACTIVITY NUMBER: T05CM03778
PROJECT NAME: Addition - Sam Levitz Furniture
PROJECT ADDRESS: 100 N. Pantano
ARCHITECT / ENGINEER: Steve Shell
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Clarify Mezzanine above administrative area is existing.
2) Appears both women's restroom facilities entry doors do not meet accessibility requirements. Justify per section 3409.
3) Detail 204/S8 clarify spacing of epoxy bolts per sht. 34 of structural calculations.
4) Per your request via phone valuation for this addition $809,940.41.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/14/2005 DELMA ROBEY OUT TO CUSTOMER Completed
09/14/2005 SUE REEVES REJECT SHELF Completed