Permit Number - T05CM03773
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/18/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/18/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 07/18/2005 | JOSE ORTIZ | ENGINEERING | REVIEW | Approved | |
| 08/02/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM03773 8/2/05 1. Minimum font size 1/8". 2. Identify panel and circuit number for proposed receptacles. Account for them on panel schedule. |
| 08/26/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/26/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | 1) Provide restroom facilities per 2003 ANSI A117.1 2) Provide code analysis 3) Provide site plan and provide information on most restrictive use for building. 4) Provide budget on drawing for 20% cost of construction to meet ansi A117.1 2003. |
| 08/26/2005 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 08/26/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/26/2005 | ROBERT SHERRY | WATER | REVIEW | Approved |