Permit Number: T05CM03728
Parcel: 13809008A

Address:
6445 S 12TH AV

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T05CM03728
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2005 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Submit a separate landscape plan for expansion area per DS 2-07.0 Show how the site will meet current code requirements.

2. Street landscape borders shall be a minimum of ten (10) feet wide as measured from the street property line. On streets designated as Major Streets and Routes (MS&R), the street landscape border is measured from the MS&R right-of-way line as determined by Sec. 2.8.3.4. Dimension landscape borders accordingly

3. Fifty (50) percent or more of the area of the street landscape border must be covered with shrubs or vegetative ground cover. The required ground coverage must be achieved within two (2) years from the date of planting. (20) Percent of the required landscaping is to be five- (5) gallon container size or larger.

4. The planting plan and layout calculations will include location, sizes, and name of existing vegetation to remain in place per DS 2-07.2.2.A.1.e

5. Indicate square footage of all landscaped areas and calculation of the percentage of vegetative coverage on the landscape plan per DS 2-07.2.2.2.g.

Additional comments may apply
10/24/2005 ANDREW CONNOR NPPO REVIEW Approved Exception
10/26/2005 JIM EGAN FIRE REVIEW Approved
11/06/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: November 6, 2005
ACTIVITY NUMBER: T05CM03728
PROJECT NAME: Volk Company
PROJECT ADDRESS: 6445 South 12th Avenue
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN

1. It is difficult to determine where the property lines are for this parcel. Revise the plan to clearly indicate where the parcel lot lines are.

2. Add Lot dimensions to the proposed development. This comment was from the first review. Because it is difficult to see where the lot lines are located on the site plan, the lot dimensions can not be determined. Revise the plan as necessary. DS 2-02.2.1.A.5.

3. Dimension from street centerline the existing and future curb and sidewalk for Valencia Road. DS 2-02.2.1.A.21.

4. The next submittal can be reviewed over the counter since there is only 3 comments. Please contact Patricia Gilbert at 791-5550, extension 2206, for scheduling and/or any questions.
11/07/2005 DAN CASTRO ZONING HC SITE REVIEW Denied Accessible on-site pedestrain circulation path is required from the propsoed building to the right-of-way and to the on-site pedestrian circulatuion system providing pedestrian access to the rest of the shopping center.
11/07/2005 DAN CASTRO ZONING REVIEW Denied COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Copies of the previously approved site plans do not show separate lots within the shopping center. Per Pima County Assessors records, the subject property was split in 1979. At time of lot split a vehicular and pedestrian cross access agreement would have been required. None of the site plans indicate a cross access agreement or easement is in place. Provide documentation of the existing vehicle and pedestrian cross access agreement or if one is not found a recorded vehicular and pedestrian cross access agreement will be required to be submitted prior to site plan approval. The docket and page of the agreement and a description of the agreement or easement shall be noted on the plan.

2. Demonstrate maneuverability into out of the loading zone and obtain Engineering approval. (D.S. 2-02.2.1.A.14) (D.S. 2-02.2.2.A.5_(LUC 3.4.5)

3. Dimension existing and future right-of-way and curb along 12th Avenue. Contact the Engineering Section reviewer on possible intersection widening that may increase the ½ right-of-way width to 75 feet and how that would impact future right-of-way and curb locations. (D.S. 2-02.2.1.A.19)

4. Where is the on-site pedestrian circulation connection required in the previous comment? The new building must be connected to the rest of the shopping center through a minimum four (4) foot on-site sidewalk. (D.S. 2-08)

5. Add lot lines, dimensions, and bearing for the subject property.

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608 ext. 1180. An appointment is required to discuss these comments in person.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/06/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
12/06/2005 SUE REEVES REJECT SHELF Completed