Permit Number: T05CM03696
Parcel: 141153540

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03696
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2005 LOREN MAKUS ENGINEERING REVIEW Approved
07/13/2005 HEATHER THRALL ZONING REVIEW Approved
07/14/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/14/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. CLARIFY TOILET REQUIREMENTS PER IBC SEC 29 REQUIRES 2 ACCESSIBLE TOILET ROOMS WHEN OCCUPANT LOAD EXCEEDS 15.
S2. CLARIFY CONNECTION OF BRACES TO TOP OF PARTITION AND TO STRUCTURE ABOVE ( SHOW FASTENER TYPE SIZE SPACING/NUMBER).
S3. CLARIFY SEPARATION REQUIEMENTS ,PER IBC SEC 3, OF TENANT SPACES , SHOW ADJACENT TENANT SPACE OCCUPANCIES.
S4. SHOW USE OF RAISED AREA AND SHOW ACCESSIBILITY, AS NECCESSARY.
07/14/2005 ROBERT SHERRY WATER REVIEW Approved
07/14/2005 JIM EGAN FIRE REVIEW Approved
07/14/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/14/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM03696 7/14/05

Lighting Plan shows new lights on Ckt P3-12. Existing receptacles are on this circuit. No circuit for new lighting is indicated on electrical panel.
07/19/2005 JMORALE1 WWM REVIEW Needs Review