Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the size of the trap and trap arm from the lavatory to a maximum of 1-1/2". Reference Table 7-3 footnote, UPC 1994.
2. Show how the existing building drains are oriented in the area where they are being tied in to.
3. Provide a shut off valve for the new water supply to the building.
4. Show the location of the meter and the RPBP relative to the new piping.