Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T05CM03659
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the trap and trap arm from the lavatory to a maximum of 1-1/2". Reference Table 7-3 footnote, UPC 1994. 2. Show how the existing building drains are oriented in the area where they are being tied in to. 3. Provide a shut off valve for the new water supply to the building. 4. Show the location of the meter and the RPBP relative to the new piping. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/08/2005 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 09/08/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |