Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM03659
Parcel: 13314459C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03659
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM03659 7/18/05

1. Specify grounding at new phone board per NEC 800.40.

2. Equipment grounding conductors in conduit runs 6 and 8 shall be no smaller than #6. Reference NEC Table 250.122.
07/18/2005 GERRY KOZIOL WWM REVIEW Approved
07/18/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations for AC-1 per Section
403.3.2, IMC 2000.