Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM03659
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/18/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM03659 7/18/05 1. Specify grounding at new phone board per NEC 800.40. 2. Equipment grounding conductors in conduit runs 6 and 8 shall be no smaller than #6. Reference NEC Table 250.122. |
| 07/18/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 07/18/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations for AC-1 per Section 403.3.2, IMC 2000. |