Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM03659
Parcel: 13314459C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03659
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2005 JIM EGAN FIRE REVIEW Approved
07/13/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/13/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
07/13/2005 ROBERT SHERRY WATER REVIEW Approved
07/13/2005 HEATHER THRALL ZONING REVIEW Approved
07/13/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations per Section 403.3, IMC 2000. The area of the rooms should be the actual room area.
2. Show how the exhaust fans for the restroom are to be controlled to prevent recirculation of the air from the restrooms.
07/13/2005 LOREN MAKUS ENGINEERING REVIEW Approved
07/18/2005 JMORALE1 WWM REVIEW Needs Review
07/18/2005 JMORALE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review