Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM03659
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/13/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/13/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/13/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/13/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/13/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 07/13/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation calculations per Section 403.3, IMC 2000. The area of the rooms should be the actual room area. 2. Show how the exhaust fans for the restroom are to be controlled to prevent recirculation of the air from the restrooms. |
| 07/13/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 07/18/2005 | JMORALE1 | WWM | REVIEW | Needs Review | |
| 07/18/2005 | JMORALE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |