Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM03657
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/13/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
07/13/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM03657 7/13/05 1. Fill in electrical load for existing receptacles on new panel, and add to total load calculations. 2. Note indicates that all existing receptacles are to be removed in demolition, which conflicts with the connection of existing receptacles on the new panel. Please clarify. 3. Provide size for the feeder to new Panel A. 4. On Keynote 4 Single Line Riser it appears that this disconnect is intended for the new panel. As a 200A disconnect it would not have a 300AF. 5. Please document contact person who stated that this service has less than 10,000A AFC, or add a note to the plans requiring the Contractor to provide such documentation. |
07/13/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
07/13/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
07/14/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
07/14/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | S1. CLARIFY ACCESSIBLITY COMPLIES TO 20 PERCENT REQUIRED BY IBC SEC 34. S2. CLARIFY SEPARATION REQUIREMENTS BETWEEN B-OFFICE AND S1-STORAGE. S3. CLARIFY TOTAL SQUARE-FOOTAGE OF THE TENANT SPACE AND OCCUPANCIES, AS APPROPRIATE. S4. CLARIFY CONNECTION OF BRACES TO TOP OF PARTITIONS AND TO STRUCTURE ABOVE ( SHOW FASTENER TYPE, SIZE, NUMBER/SPACING) |
07/14/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/14/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate the design shown on M1 with the information shown on M2. 2. Show ventilation calculations. 3. Clarify how the air is to return to the south A/C unit. 4. Clarify the relationship of AC1, HP1 and FC1. |
07/18/2005 | GERRY KOZIOL | WWM | REVIEW | Completed |