Permit Number: T05CM03657
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03657
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2005 JIM EGAN FIRE REVIEW Approved
07/13/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM03657 7/13/05

1. Fill in electrical load for existing receptacles on new panel, and add to total load calculations.
2. Note indicates that all existing receptacles are to be removed in demolition, which conflicts with the connection of existing receptacles on the new panel. Please clarify.
3. Provide size for the feeder to new Panel A.
4. On Keynote 4 Single Line Riser it appears that this disconnect is intended for the new panel. As a 200A disconnect it would not have a 300AF.
5. Please document contact person who stated that this service has less than 10,000A AFC, or add a note to the plans requiring the Contractor to provide such documentation.
07/13/2005 HEATHER THRALL ZONING REVIEW Approved
07/13/2005 LOREN MAKUS ENGINEERING REVIEW Approved
07/14/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/14/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. CLARIFY ACCESSIBLITY COMPLIES TO 20 PERCENT REQUIRED BY IBC SEC 34.
S2. CLARIFY SEPARATION REQUIREMENTS BETWEEN B-OFFICE AND S1-STORAGE.
S3. CLARIFY TOTAL SQUARE-FOOTAGE OF THE TENANT SPACE AND OCCUPANCIES, AS APPROPRIATE.
S4. CLARIFY CONNECTION OF BRACES TO TOP OF PARTITIONS AND TO STRUCTURE ABOVE ( SHOW FASTENER TYPE, SIZE, NUMBER/SPACING)
07/14/2005 ROBERT SHERRY WATER REVIEW Approved
07/14/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate the design shown on M1 with the information shown on M2.
2. Show ventilation calculations.
3. Clarify how the air is to return to the south A/C unit.
4. Clarify the relationship of AC1, HP1 and FC1.
07/18/2005 GERRY KOZIOL WWM REVIEW Completed