Permit Number: T05CM03610
Parcel: 11105063J

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03610
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2005 JIM EGAN FIRE REVIEW Approved
08/09/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/09/2005 HEATHER THRALL ZONING REVIEW Approved
08/09/2005 ROBERT SHERRY WATER REVIEW Approved
08/09/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/10/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review
08/10/2005 GBONILL1 WWM REVIEW Needs Review
08/10/2005 GBONILL1 ENGINEERING REVIEW Needs Review
08/10/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM03610 8/9/05

1. In fault calculations, "RK-2" needs to be changed to read "RK-1."
2. 20AFs would not allow the new HPs to start. Note that MOCP is 30A.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/10/2005 GBONILL1 OUT TO CUSTOMER Completed