Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM03610
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/09/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/09/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/09/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 08/09/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/09/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/10/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 08/10/2005 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 08/10/2005 | GBONILL1 | ENGINEERING | REVIEW | Needs Review | |
| 08/10/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM03610 8/9/05 1. In fault calculations, "RK-2" needs to be changed to read "RK-1." 2. 20AFs would not allow the new HPs to start. Note that MOCP is 30A. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/10/2005 | GBONILL1 | OUT TO CUSTOMER | Completed |