Permit Number: T05CM03610
Parcel: 11105063J

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03610
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2005 JIM EGAN FIRE REVIEW Approved
07/12/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/12/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM03610 7/12/05

1. Plot location of service location. Demonstrate that the available fault current at existing Panels A and B does not exceed the rating of such panels.

2. It appears that the intent is to series rate the new CB with the branch circuit CBs in new Panel N. Please clarify.
07/12/2005 ROBERT SHERRY WATER REVIEW Approved
07/12/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide energy calculations
07/20/2005 GBONILL1 ZONING REVIEW Needs Review
07/20/2005 GBONILL1 WWM REVIEW Needs Review
07/20/2005 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
07/20/2005 GBONILL1 ENGINEERING REVIEW Needs Review