Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM03578
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2005 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Denied | GENERAL REQUIREMENTS: 1. All dimensions and notes shall be consistent on each plan or elevation: Detail #1 and the wall construction note on the right edge of sheet 3 calls for ½" OSB on all exterior walls. This is not consistent with the 3/8" OSB shown on the exterior shear wall note, sheet 3 and detail #1, sheet 6. Show one size or clearly show the locations of each size. 2. Provide sheet 10 or renumber all sheets showing a total of 9 sheets. 3. Remove incorrect square footage figures from sheets 2 & 3 4. Change the detail reference for the shear panel on sheet 2 to read 3/3 typ. 5. Change the 2 x 4 dimensional lumber notation on details 3/3 & 4/5 to be consistent with other wall sizing of 2 x 6. R-19 batt insulation may not be installed in 2 x 4 spacing. 6. Correct the inconsistencies between the header schedule sheets 3 & 6 and the opening schedule sheet 5. 7. Remove the optional fireplace note from sheet 3 if an ICBO evaluation report is not provided. STRUCTURAL PLANS: 1. Locate brace wall panels at each wall line end and (west wall) centered at least every 25', Table R602.10.1. ELEVATIONS: 1. Calculate the attic ventilation area using the correct attic area in compliance with R806.2. Note size and location of all vents needed to comply. Note only 80% of the required ventilating area may be provided by ridge or gable vents when applying the reduced area calculation. Also, reduce the effective gable openings by any restrictive end-truss members. Show the amount of eave vents needed to comply. 2. Show a minimum 1" vent clearance between ceiling insulation and roof sheathing if insulation is attached to truss bottom cord and rafter venting is used, R806.3. This may be accomplished w/ baffles. SECTIONS - DETAILS - MISC. NOTES: 1. Note the post foundation specifications on section B-B, sheet 5, or reference detail 3/6 if the patio posts are framed for stucco finishing. 2. Ceiling gypsum board shall be either 5/8" or ½" sag resistant when applied to 24" o.c. framing (note at section A-A, sheet 5 and detail 7/6), IRC table R702.3.5 footnote d. PLUMBING PLANS: 1. The City of Tucson has adopted the 2003 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). Change the drainage system note to reference this code. Correct references to the 1994 UPC and the 2000 or 2003 IRC on sheet 7. 2. Remove the Water Supply Demand schedule from the left side of sheet 7, and correct the water fixture schedule (right side) using 2003 UPC Table 6-4 values: tub/shower 2 becomes 4 w/ a total of 8 shower (alone) is now 2 w/ a total of 2 hose bibb 3 becomes 2.5 + 1 each additional w/ a total of 4.5 lavatory 1 is correct w/ a total of 4 sink 2 becomes 1.5 w/ a total of 1.5 dishwasher is 1.5 for a new entry of 1.5 water closet 3 becomes 2.5 w/ a total of 5 clothes washer 6 becomes 4 w/ a total of 4 laundry tub 2 is correct w/ a total of 2 Show the new total of 32.5 fixture units which requires a minimum of a 1" main line. Provide the maximum developed length of water line from the meter to furthest fixture and use Table 6-5 for determining the main line size. 3. Remove the laundry sink from the floor plan, sheet 2 and water isometric, sheet 7, or add the sink to the plumbing plan, sewer isometric and fixture connection schedule. 4. Add the clothes washer to the sewer isometric, sheet 7. MECHANICAL PLANS: 1. Verify the location of the 12" x 36" return air register shown on the furnace room detail. 2. Verify the manufacturer's required clearance for the furnace unit, M1402.2 3. Combustion air openings shall be unobstructed for a distance of not less than 6" in front of the opening, M1402.3. ELECTRICAL PLANS: 1. Indicate the location and circuit number of the evap cooler disconnect switch and furnace air handler. 2. The bathroom receptacles shall be on a separate 20 AMP circuit with no other outlets (lights), E3603.4. The master bath receptacles (GFCI) may be placed on the same circuit as the other bathroom receptacles #7. If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/16/2005 | GBONILL1 | OUT TO CUSTOMER | Completed |
| 12/16/2005 | SUE REEVES | REJECT SHELF | Completed |