Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM03568
Parcel: 10309064B

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T05CM03568
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2005 JIM EGAN FIRE REVIEW Approved
08/31/2005 GLENN MOYER PLANNING-CITY HALL REVIEW Denied Please add the following notes:

Noise associated with the new generator shall not exceed 85 dB(A) between 7:00am and 10:00pm and 70 dB(A) between 10:00pm and 7:00am at the property line.

The new generator shall be for emergency use only, and shall not be used on a daily basis.
09/09/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information to show that the installation of the generator conforms to the requirements of NFPA 37 with regard to the fuel supply (Sections 6.1 and 6.3) and controls and instrumentation (Chapter 9). Reference Section 915, IMC 2000.
09/29/2005 JAY HOGAN OPERATIONS REVIEW Approved
10/03/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 10/4/05
ACTIVITY NUMBER: T05CM03568
PROJECT NAME: Cell Tower
PROJECT ADDRESS: 2370 W. River Park Dr.
ARCHITECT / ENGINEER: L/D Architects
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Provide structural calculations that the slab can support the generator equipment. Justify depth of footing see section 1805.2.

2) Clarify / justify seperated or non-seperated use section 302.3.1 & 302.3.2 between existing equipment shelter or incidental use area table 302.1.1 - Emergency generator.
10/04/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/05/2005 DAN CASTRO ZONING REVIEW Denied Zoning Review section has reviewed the plans and may approve the plans after Glenn Moyer has approved them for Special Exception review compliance. Upon obtaining approval from Glenn Moyer, the plans may be reviewed at the counter by the Zoning Review section only. Please contact me at 791-5608 ext. 1180 to set an appointment.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
10/25/2005 SUE REEVES REJECT SHELF Completed