Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM03484
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/14/2005 | MATT FLICK | ENGINEERING | REVIEW | Approved | |
10/21/2005 | DAN CASTRO | ZONING | REVIEW | Denied | 1. A copy of the zoning review stamped approved site plan must be inserted into the building plans set. The site plan was approved on October 5, 2005 by Zoning. The current site plan submitted with the building plans set does not have the zoning review approval stamp. 2. Revise the maximum building hegiht noted on the site plan to match the maximum building height dimensioned on the elevation drawings. Building height is measured from design grade. |
10/24/2005 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |