Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM03484
Parcel: 13219015B

Address:
2220 E BENSON HY

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T05CM03484
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2005 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. The landscape plan will contain the following identification: property lines, and correct Legal description per DS 2-07.2.1.B

2. An unpaved planting area, which is a minimum of 34 square feet in area and 4 feet in width, must be provided for each canopy tree within vehicle use area per LUC 3.7.2.3.A.1.c. Dimension planter areas on landscape plans, canopy tree adjacent to building appears to be less than 4' wide. Clarify width or relocate tree.

3. Landscaping within parking lots where plants are susceptible to injury by vehicular traffic must be protected by appropriate means, such as curbs, bollards, or low walls per LUC 3.7.2.3.B. Provide protection for canopy tree within vehicle use area to the east.
09/23/2005 JOE LINVILLE NPPO REVIEW Approved Exception
09/29/2005 LOREN MAKUS ENGINEERING REVIEW Denied DATE: September 29, 2005
TO: Rob Caylor; Robert Caylor Construction
SUBJECT: BTE Ventures, LLC, 2220 E Benson Highway; Site Plan and Grading Plan Review
REVIEWER: Loren Makus, E.I.T.
ACTIVITY NUMBERS: T05CM03484

SUMMARY: The Site Plan and Grading Plan were reviewed by Development Services Department Engineering Division and was not approved at this time. Revise the Site Plan and Grading Plan in accordance with the following comments.
Site Plan comment:
1. Provide general dimensions and a representative cross-section for the depressed planting areas. This must be presented on both the site plan and the grading plan. The basin details must be consistent with the submitted drainage report.

Revise the Site Plan and the Grading Plan to address all of these comments and resubmit two copies of the Site Plan and two copies of the drainage report. If you have any questions or if you would like to meet with me to discuss any of these comments please call me at (520) 791-5550 ext. 1161 or email me at loren.makus@tucsonaz.gov.

Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services
10/06/2005 DAN CASTRO ZONING HC SITE REVIEW Approved
10/06/2005 DAN CASTRO ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/10/2005 JMORALE1 OUT TO CUSTOMER Completed
10/10/2005 SUE REEVES REJECT SHELF Completed