Permit Number: T05CM03484
Parcel: 13219015B

Address:
2220 E BENSON HY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03484
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) need approved site plan before permit can be released.
09/13/2005 LOREN MAKUS ENGINEERING REVIEW Denied Building Plans may not be approved prior to Site Plan approval. A copy of the approved site plan shall be inserted into building plan set.
09/14/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please provide a disconnect for the Insta-Hot per NEC 422 Part III.
2. Please identify circuits for the Evaporative Cooler Maintenance Receptacle, and the Evaporative Cooler Pump. This comment was made on the initial submittal, but we don't see that this has been done.
3. EC-1 is listed as 460V on Sheet M-1and on the Power Plan. According to the panel schedule and line diagram on Sheet E-3, this is to be a 208V unit. Please coordinate with Mechanical and clarify.
09/19/2005 DAN CASTRO ZONING REVIEW Denied Building Plans may not be approved prior to Site Plan approval. A copy of the approved site plan shall be inserted into building plan set.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/20/2005 GBONILL1 OUT TO CUSTOMER Completed