Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/08/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) need approved site plan before permit can be released. |
09/13/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | Building Plans may not be approved prior to Site Plan approval. A copy of the approved site plan shall be inserted into building plan set. |
09/14/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Please provide a disconnect for the Insta-Hot per NEC 422 Part III. 2. Please identify circuits for the Evaporative Cooler Maintenance Receptacle, and the Evaporative Cooler Pump. This comment was made on the initial submittal, but we don't see that this has been done. 3. EC-1 is listed as 460V on Sheet M-1and on the Power Plan. According to the panel schedule and line diagram on Sheet E-3, this is to be a 208V unit. Please coordinate with Mechanical and clarify. |
09/19/2005 | DAN CASTRO | ZONING | REVIEW | Denied | Building Plans may not be approved prior to Site Plan approval. A copy of the approved site plan shall be inserted into building plan set. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/20/2005 | GBONILL1 | OUT TO CUSTOMER | Completed |