Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM03484
Parcel: 13219015B

Address:
2220 E BENSON HY

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM03484
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Water fountain per table 2902.1 .
2) Restrooms 1 per each sex. Accessibility per 1104.3. Why one sex required to go through shop space to reach the restroom?
3) Special Inspection for field welding needs to be provided before release of permit.
4) Approved site plan before permit can be released.
08/03/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Sheet P-1 calls for an Insta-Hot in the vicinity of the bathrooms. Please add to electrical plans.
2. On Panel Schedule L, please label Ckt 1 as Lights and EFs, not receptacles.
3. Please identify circuits for the Evaporative Cooler Maintenance Receptacle, and the Evaporative Cooler Pump.
4. Note that minimum font size is 1/8'. Enlarge as necessary/convenient, and please keep this in mind on future projects.
08/05/2005 DAN CASTRO ZONING REVIEW Denied Zoning Review Section may not approve the building plans prior to site plan approval. Site plan is currently under review. Please assure that all structures shown on the building plans match the location, size, and height on the site plan.
08/10/2005 LOREN MAKUS ENGINEERING REVIEW Denied The site plan must be approved before Engineering can approve the building plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/23/2005 KMEDINA1 OUT TO CUSTOMER Completed