Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM03457
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/13/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/14/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/09/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 08/10/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM03457 8/5/05 1. Indicate on the plans that Lift is for future, if such is the case. 2. Specify mounting height of new electrical equipment, such that it is in compliance with NEC Article 511. 3. Provide power requirements for new Air Compressor. 4. Specify the wiring method in the spaces above the Class I locations. It is not possible for the Plans Examiner to determine compliance with NEC 511.7 5. Identify on the plans any area which is to be classified. Reference NEC 511.3. 6. Provide 2 sets of plans. |
| 08/11/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/11/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 08/11/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/11/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 08/16/2005 | GERRY KOZIOL | WWM | REVIEW | Approved |