Permit Number: T05CM03457
Parcel: 113082050

Address:
2842 N 1ST AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03457
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
07/14/2005 JIM EGAN FIRE REVIEW Approved
08/09/2005 HEATHER THRALL ZONING REVIEW Approved
08/10/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM03457 8/5/05

1. Indicate on the plans that Lift is for future, if such is the case.
2. Specify mounting height of new electrical equipment, such that it is in compliance with NEC Article 511.
3. Provide power requirements for new Air Compressor.
4. Specify the wiring method in the spaces above the Class I locations. It is not possible for the Plans Examiner to determine compliance with NEC 511.7
5. Identify on the plans any area which is to be classified. Reference NEC 511.3.
6. Provide 2 sets of plans.
08/11/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/11/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
08/11/2005 ROBERT SHERRY WATER REVIEW Approved
08/11/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/16/2005 GERRY KOZIOL WWM REVIEW Approved